EN50288-7 Cables
XLPE Insulated, LSZH Sheathed Instrumentation Cables

EN 50288-7 Cables

XLPE Insulated, LSZH Sheathed & Overall Screened Instrumentation Cables (Multitriple)

RE-2X(St)H 90°C / 300 V

APPLICATION:

EN 50288-7 cables are used for transmission of analoge and digital signals in instrument and control systems at

chemistry and petrochemistry industry plants, power plants, natural gas and petroluem plants, etc... EN 50288-7

cables are used in the environments which have no corrosive gases are emitted in the event of fire. In case of

fire, EN 50288-7 cables inhibit the propagation of the flames whereby the development of smoke is extremely

low.

EN 50288-7 Instrumentation cables are not allowed for direct connection to a low impedance sources, e.g. public

mains electricity supply. With blue sheath it is suitable for intrinsically safe systems. EN 50288-7 cables are not

recommended for direct burial.EN 50288-7 are for indoor and outdoor installation, in dry and wet locations; on

racks, trays, in conduits.

STANDARDS

RE-2X(St)H 90°C / 300 V

Basic design to EN50288-7

FIRE PERFORMANCE

Flame Retardance (Single Vertical Wire Test) EN 60332-1-2; IEC 60332-1-2; BS EN 60332-1-2; VDE 0482-332-1; NBN C 30-004 (cat. F1); NF C32-070-2.1(C2); CEI 20-35/1-2; EN 50265-2-1*; DIN VDE 0482-265-2-1*
Reduced Fire Propagation(Vertically-mounted bundled wires & cable test) EN 60332-3-24 (cat. C); IEC 60332-3-24; BS EN 60332-3-24; VDE 0482-332-3; NBN C 30-004 (cat. F2); NF C32-070-2.2(C1); CEI 20-22/3-4; EN 50266-2-4*; DIN VDE 0482-266-2-4
Halogen Free IEC 60754-1; EN 50267-2-1; DIN VDE 0482-267-2-1; CEI 20-37/2-1 ; BS 6425-1*
No Corrosive Gas Emission IEC 60754-2; EN 50267-2-2; DIN VDE 0482-267-2-2; CEI 20-37/2-2 ; BS 6425-2*
Minimum Smoke Emission IEC 61034-1&2; EN 61034 -1&2; DIN VDE 0482-1034-1&2; CEI 20-37/3-1&2; EN 50268-1&2*; BS 7622-1&2*
No Toxic gases NES 02-713; NF C 20-454
Sunlight Resistance UL 1581 section 1200
Oil Resistance ICEA S-73-532**

Note: Asterisk * denotes superseded standard, ** denotes Test temperature +60°C, duration 4h. Retention: min 60% of tensile

strength/min.60% of elongation, *** denotes optional.

VOLTAGE RATING

300V

CABLE CONSTRUCTION

Conductor: Annealed copper solid or plain copper stranded to IEC 60228 Class 2.

Insulation: Extruded cross-linked XLPE compound, EN 50290. 2-29.

Triple: Three conductors twisted to form a triple

Lay-up: Triples laid up in layers of optimum pitch

Separator: Polyester tape

Overall Screen: Aluminium/polyester tape with tinned copper drain wire, 0.5mm2

Outer Sheath: Thermoplastic LSZH compound type LTS3 as per BS 7655-6.1 (Thermosetting LSZH compound

type SW2-SW4 as per BS 7655-2.6 can be offered.). UV resistance, hydrocarbon resistance, oil resistance, anti

rodent and anti termite properties can be offered as option.

COLOUR CODE

Insulation: Black / White / Red, continuously numbered on white core(1, 2..)for multitriples.

Outer Sheath: Black or blue for intrinsically safe systems

Physical AND THERMAL PROPERTIES

Temperature Range During Operation (Fixed State): -30°C – +90°C

Temperature Range During Installation (Mobile State): -5°C – +50°C

Minimum Bending Radius: 7.5 X Overall Diameter

Electrical PROPERTIES

Conductor Area Size mm 2 0.5 0.75 1.0 1.3 1.5
Insulation thickness (nominal) mm 0.35 0.38 0.4 0.45 0.45
Conductor resistance (20°C)  Ω/km 36.7 25.0 18.5 14.2 12.3
Insulation resistance (20°C) MΩ.km(Min.) 5000
Mutual Capacitance (1 kHz) up to 4 trples pF/m(Max.) 90 90 90 102 102
  above 4 trples pF/m(Max.) 75 75 75 85 85
Inductance mH/km(Max.) 1
L / R (ratio) (max.) μH/Ω 25 25 25 40 40
Operating voltage V 300
Test Voltage Urms  Core to Core V 1500
Core to Screen V 1500

CONSTRUCTION PARAMETERS

Caledonian Cable Code

RE-2X(St)H

 

No. of Triples x3xCross Section

Nominal Insulation Thickness

Nominal Outer Sheath Thickness

 

No.x3xmm2

mm

mm

0.5mm2 , Multi-striple

RE-2X(St)H 2T0.5

2x3x0.50

0.35

0.9

RE-2X(St)H 4T0.5

4x3x0.50

0.35

1.0

RE-2X(St)H 5T0.5

5x3x0.50

0.35

1.0

RE-2X(St)H 6T0.5

6x3x0.50

0.35

1.0

RE-2X(St)H 8T0.5

8x3x0.50

0.35

1.1

RE-2X(St)H 10T0.5

10x3x0.50

0.35

1.1

RE-2X(St)H 12T0.5

12x3x0.50

0.35

1.1

RE-2X(St)H 16T0.5

16x3x0.50

0.35

1.2

RE-2X(St)H 20T0.5

20x3x0.50

0.35

1.2

RE-2X(St)H 24T0.5

24x3x0.50

0.35

1.3

0.75mm2 , Multi-striple

RE-2X(St)H 2T0.75

2x3x0.75

0.38

0.9

RE-2X(St)H 4T0.75

4x3x0.75

0.38

1.0

RE-2X(St)H 5T0.75

5x3x0.75

0.38

1.0

RE-2X(St)H 6T0.75

6x3x0.75

0.38

1.1

RE-2X(St)H 8T0.75

8x3x0.75

0.38

1.1

RE-2X(St)H 10T0.75

10x3x0.75

0.38

1.2

RE-2X(St)H 12T0.75

12x3x0.75

0.38

1.2

RE-2X(St)H 16T0.75

16x3x0.75

0.38

1.3

RE-2X(St)H 20T0.75

20x3x0.75

0.38

1.3

RE-2X(St)H 24T0.75

24x3x0.75

0.38

1.4

RE-2X(St)H 2T1.0

2x3x1.0

0.4

1.0

RE-2X(St)H 4T1.0

4x3x1.0

0.4

1.0

RE-2X(St)H 5T1.0

5x3x1.0

0.4

1.0

RE-2X(St)H 6T1.0

6x3x1.0

0.4

1.1

RE-2X(St)H 8T1.0

8x3x1.0

0.4

1.1

RE-2X(St)H 10T1.0

10x3x1.0

0.4

1.2

RE-2X(St)H 12T1.0

12x3x1.0

0.4

1.2

RE-2X(St)H 16T1.0

16x3x1.0

0.4

1.3

RE-2X(St)H 20T1.0

20x3x1.0

0.4

1.4

RE-2X(St)H 24T1.0

24x3x1.0

0.4

1.4

1.3mm2 , Multi-striple

RE-2X(St)H 2T1.3

2x3x1.3

0.45

1.0

RE-2X(St)H 4T1.3

4x3x1.3

0.45

1.1

RE-2X(St)H 5T1.3

5x3x1.3

0.45

1.1

RE-2X(St)H 6T1.3

6x3x1.3

0.45

1.2

RE-2X(St)H 8T1.3

8x3x1.3

0.45

1.2

RE-2X(St)H 10T1.3

10x3x1.3

0.45

1.3

RE-2X(St)H 12T1.3

12x3x1.3

0.45

1.3

RE-2X(St)H 16T1.3

16x3x1.3

0.45

1.4

RE-2X(St)H 20T1.3

20x3x1.3

0.45

1.5

RE-2X(St)H 24T1.3

24x3x1.3

0.45

1.6

1.5mm2 , Multi-striple

RE-2X(St)H 2T1.5

2x3x1.5

0.45

1.0

RE-2X(St)H 4T1.5

4x3x1.5

0.45

1.1

RE-2X(St)H 5T1.5

5x3x1.5

0.45

1.1

RE-2X(St)H 6T1.5

6x3x1.5

0.45

1.2

RE-2X(St)H 8T1.5

8x3x1.5

0.45

1.3

RE-2X(St)H 10T1.5

10x3x1.5

0.45

1.3

RE-2X(St)H 12T1.5

12x3x1.5

0.45

1.4

RE-2X(St)H 16T1.5

16x3x1.5

0.45

1.5

RE-2X(St)H 20T1.5

20x3x1.5

0.45

1.6

RE-2X(St)H 24T1.5

24x3x1.5

0.45

1.7

       

Note : Other conductor sizes & core configurations are available upon request.